Analisis Indeks Keandalan Secara Teknis Dan Ekonomis Jaringan Distribusi 20 kV Menggunakan Metode Section Tekhnique Pada PT.PLN (Persero) Rayon Belawan

Gunawan Sihombing, Universitas Amir Hamzah, Indonesia

Abstract


ABSTRACT
The purpose of this study is to analyze the reliability index of SAIDI, SAIFI and CAIDI using the Section Technique method and evaluate the reliability according to the IEEE Std 1366-2003 Reliability Index Standard. PLN (Persero) Belawan District. Based on the results of the reliability index analysis using the section technique method, the SAIFI reliability index value for the Lamhotma 01 feeder (LH01) is 1.6 times customers/year, exceeding the standard set by IEEE Std 1366-2003 which is 1.45 times customers/year, and meets the standard. SPLN is set at 3.0 times customers/year. The SAIDI value of the Lamhotma 01 feeder (LH01) is 2.0 hours/year. 6 hours/customer exceeds the standard set by IEEE-1366-2003 which is 1.47 hours/customer and exceeds the standard set by SPLN. And the energy that is not distributed (ENS) due to the blackout at the Lamhotma feeder in 2021 is 32681.33 kWh and the average energy is not channeled 4.7 kWh / customer and the economic loss is estimated at Rp 40,105.090.00.

ABSTRAK

Tujuan penelitian ini adalah menganalisis indeks keandalan SAIDI, SAIFI dan CAIDI menggunakan metode Section Technique  dan mengevaluasi keandalan sesuai dengan Standar Indeks Keandalan IEEE Std 1366 – 2003. Mengetahui rata-rata energi yang tidak tersalurkan secara teknis dan ekonomis  akibat terjadinya pemadaman di PT. PLN (Persero) Rayon Belawan. Berdasarkan hasil analisis indeks keandalan dengan menggunakan metode section tekhnique nilai indeks keandalan SAIFI penyulang Lamhotma 01 (LH01)  adalah 1,6 kali pelanggan/tahun melebihi standar yang ditetapkan oleh IEEE Std 1366-2003 yaitu 1,45 kali pelanggan/tahun, dan memenuhi standar yang di tetapkan SPLN sebesar 3,0 kali pelanggan/tahun. Nilai SAIDI penyulang Lamhotma 01 (LH01) adalah Sebesar 2,0 jam/tahun memenuhi standar  yang telah di tetapkan IEEE std 1366-2003 yaitu 2.30 jam/tahun, dan juga memenuhi standar SPLN, dan nilai CAIDI penyulang Lamhotma (LH01) adalah 4,6 jam/pelanggan melebihi standar yang di tetapkan IEEE-1366-2003 yaitu 1,47 Jam/pelanggan, dan juga melebihi standar yang di tetapkan SPLN. Serta energi yang tidak tersalurkan (ENS) akibat terjadinya pemadaman pada penyulang Lamhotma tahun 2021 sebesar 32681,33 kWh dan rata-rata energi tak tersalurkan 4,7 kwh/pelanggan dan kerugian ekonomis diperkirakan sebesar Rp 40.105.090,00.





Keywords


Reliability, Feeder, SAIFI, SAIDI and CAIDI

Full Text:

PDF

References


B. Pada, R. Bidang, & D. Metode. (2016). Method of Sections.

Brown, R. E. (2017). Electric power distribution reliability. CRC press.

Dasman, D., & Handayani, H. (2017). Evaluasi Keandalan Sistem Distribusi 20 kV Menggunakan Metode SAIDI dan SAIFI di PT. PLN (Persero) Rayon Lubuk Alung Tahun 2015. Jurnal Teknik Elektro, 6(2), 170–179.

Energi, D. pertambangan dan. (1985). SPLN 59 : 1985 Keandalan Sistem Distribusi.

J. K. Koster, L. H. Cohn, R. B. B. Mee, & J. J. Collins. (1978). Reliability Evaluation of Power Systems. 26(5).

Kobayashi, Y. (2016). Distributed Power Generation. In Hydrogen Energy Engineering (pp. 483–496). Springer.

Praditama, F., Utomo, T., & Shidiq, M. (2014). ANALISIS KEANDALAN DAN NILAI EKONOMIS DI PENYULANG PUJON PT. PLN (PERSERO) AREA MALANG. Jurnal Mahasiswa TEUB, 2(6).

Pramono, J. (2010). Makalah Teknik Tenaga Listrik, Transmission of Electrical Energy (Transmisi Tenaga Listrik). Departe-Men Teknik Elektro, Fakultas Teknik, Universitas Indonesia, Depok. Diambil Dari Http://Staff. Ui. Ac. Id/System/Files/Users/Chairul. Hudaya/Material/Papertransmissionofelectricalenergy. Pdf.

Pratama, N. E. (2019). ANALISA GANGGUAN SALURAN UDARA TEGANGAN MENENGAH (SUTM) 20 KV PENYULANG RAYA 14 DI PT. PLN (PERSERO) AREA PONTIANAK. Jurnal Teknik Elektro Universitas Tanjungpura, 1(1).

Putra, D. E., & Nurhadiyanto, M. (2019). Analisis Keandalan Penyulang Pajajaran 20kv Menggunakan Metode Section Technique untuk Asian Games XVIII di Palembang. Jurnal Ampere, 4(1), 222–240.

R. Syahputra. (2016). Sistem Tenaga Listrik. ELTEK, 11(01), 1–293.

Standard, I. E. E. (2003). STD 1366-2003, IEEE Draft Guide for Electric Power Distribution Reliability Indices. IEEE.

Stevenson, W. D., & William, D. (1993). Analisis Sistem Tenaga Listrik Edisi Keempat. Erlangga, Jakarta.

VOLY, H. (2020). ANALISIS NILAI KEANDALAN DAN NILAI EKONOMI SISTEM JARINGAN DISTRIBUSI 20 kV PADA PT. PLN (PERSERO) RAYON DURI MENGGUNAKAN METODE FMEA (FAILURE MODE EFFECT ANALYSIS) (Doctoral dissertation, UNIVERSITAS ISLAM NEGERI SULTAN SYARIF KASIM RIAU).




DOI: https://doi.org/10.21831/jee.v6i2.53946

Refbacks

  • There are currently no refbacks.


Copyright (c) 2022 Jurnal Edukasi Elektro

Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

Indexed by:

Supported by:

RJI Main logo

Lisensi Creative Commons

JURNAL EDUKASI ELEKTRO by Jurusan Pendidikan Teknik Elektro, Fakultas Teknik UNY distributed under a Creative Commons Attribution 4.0 International License based on the copyright of https://journal.uny.ac.id/index.php/jee/.